Show simple item record

dc.contributor.authorMinnos, Bihter
dc.contributor.authorGungor, Nihal
dc.contributor.authorCotuk, Aysin
dc.contributor.authorIlhan-Sungur, Esra
dc.contributor.authorCANSEVER, Nurhan
dc.date.accessioned2021-03-05T08:30:17Z
dc.date.available2021-03-05T08:30:17Z
dc.date.issued2013
dc.identifier.citationMinnos B., Ilhan-Sungur E., Cotuk A., Gungor N., CANSEVER N., "The corrosion behaviour of galvanized steel in cooling tower water containing a biocide and a corrosion inhibitor", BIOFOULING, cilt.29, ss.223-235, 2013
dc.identifier.issn0892-7014
dc.identifier.otherav_99425617-3645-43cd-bebc-af39d570758b
dc.identifier.othervv_1032021
dc.identifier.urihttp://hdl.handle.net/20.500.12627/103069
dc.identifier.urihttps://doi.org/10.1080/08927014.2012.763117
dc.description.abstractThe corrosion behaviour of galvanized steel in cooling tower water containing a biocide and a corrosion inhibitor was investigated over a 10-month period in a hotel. Planktonic and sessile numbers of sulphate reducing bacteria (SRB) and heterotrophic bacteria were monitored. The corrosion rate was determined by the weight loss method. The corrosion products were analyzed by energy dispersive X-ray spectroscopy and X-ray diffraction. A mineralized, heterogeneous biofilm was observed on the coupons. Although a biocide and a corrosion inhibitor were regularly added to the cooling water, the results showed that microorganisms, such as SRB in the mixed species biofilm, caused corrosion of galvanized steel. It was observed that Zn layers on the test coupons were completely depleted after 3 months. The Fe concentrations in the biofilm showed significant correlations with the weight loss and carbohydrate concentration (respectively, p < 0.01 and p < 0.01).
dc.language.isoeng
dc.subjectToprak ve Bitki Besleme
dc.subjectToprak ve Su Muhafazası ve Amenajmanı
dc.subjectSu Hasadı
dc.subjectYaşam Bilimleri
dc.subjectBiyoteknoloji
dc.subjectTemel Bilimler
dc.subjectTarımsal Bilimler
dc.subjectZiraat
dc.subjectTarım ve Çevre Bilimleri (AGE)
dc.subjectBitki ve Hayvan Bilimleri
dc.subjectDENİZ VE TATLISU BİYOLOJİSİ
dc.subjectYaşam Bilimleri (LIFE)
dc.subjectMikrobiyoloji
dc.subjectBİYOTEKNOLOJİ VE UYGULAMALI MİKROBİYOLOJİ
dc.titleThe corrosion behaviour of galvanized steel in cooling tower water containing a biocide and a corrosion inhibitor
dc.typeMakale
dc.relation.journalBIOFOULING
dc.contributor.departmentYıldız Teknik Üniversitesi , Kimya-Metalurji Fakültesi , Met.Ve Malzeme Müh.Böl.
dc.identifier.volume29
dc.identifier.issue3
dc.identifier.startpage223
dc.identifier.endpage235
dc.contributor.firstauthorID2742


Files in this item

FilesSizeFormatView

There are no files associated with this item.

This item appears in the following Collection(s)